All citations for San Pablo Healthcare & Wellness Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to San Pablo Healthcare & Wellness Center

Last standard health inspection on record

June 26, 2025

Showing 1 to 17 of 17 citations

  1. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  2. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  4. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  6. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  7. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  8. No harm, with potential for more than minimal harm

    Provide primary/alternate means for communication.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0032, Emergency Preparedness Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  9. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  10. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  12. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  13. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  14. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  15. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

  17. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 11, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.