All citations for Scioto Rehabilitation & Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Scioto Rehabilitation & Care Center

Last standard health inspection on record

June 11, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  2. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 14, 2026).

  4. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  5. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 10, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (April 3, 2026).

  6. No harm, with potential for more than minimal harm

    Have proper power supply for life support equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0915, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 10, 2026. Found during a complaint inspection.

    The home has a plan to correct it.

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 10, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (April 3, 2026).

  8. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  9. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  11. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.