All citations for Seacoast Nursing and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Seacoast Nursing and Rehabilitation Center

Last standard health inspection on record

May 6, 2026

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  2. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  3. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  4. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  5. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  6. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  9. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  10. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  11. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

  13. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 3, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.