All citations for Silvis Center for Nursing Rehab & Care

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Silvis Center for Nursing Rehab & Care

Last standard health inspection on record

May 21, 2026

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2026).

  2. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 12, 2026).

  5. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  6. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 12, 2026).

  7. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  9. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  10. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  11. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  12. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

  13. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 26, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.