All citations for Skyline Healthcare Center - San Jose

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Skyline Healthcare Center - San Jose

Last standard health inspection on record

June 27, 2025

Showing 1 to 22 of 22 citations

  1. No harm, with potential for more than minimal harm

    Provide family notifications of emergency plan.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0035, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  3. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  4. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure that smoke control systems are tested and documented in accordance with established engineering principles.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0771, Miscellaneous Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  6. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  8. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of November 21, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (December 6, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of November 21, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (December 6, 2024).

  10. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  12. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  14. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  15. No harm, with potential for more than minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  16. No harm, with potential for more than minimal harm

    Establish policies and procedures for medical documentation.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0023, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  17. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  18. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  19. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  20. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  21. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  22. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.