All citations for The Eleanor Nursing Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to The Eleanor Nursing Care Center

Last standard health inspection on record

April 28, 2026

Showing 1 to 25 of 27 citations

  1. Immediate jeopardy to resident health or safety

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level L.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  2. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  3. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  4. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  5. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  6. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  7. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 5, 2024).

  8. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  9. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 27, 2024).

  10. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  12. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  13. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0531, Services Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  14. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 19, 2024).

  15. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  16. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  17. No harm, with potential for more than minimal harm

    Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0901, Electrical Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  18. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  19. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  20. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  21. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  22. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  23. No harm, with potential for minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  24. No harm, with potential for minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 2, 2024).

  25. No harm, with potential for minimal harm

    Provide family notifications of emergency plan.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0035, Emergency Preparedness Deficiencies. Inspection of September 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 27, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.