Showing 1 to 22 of 22 citations

  1. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  2. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  3. No harm, with potential for more than minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2024).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  5. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  7. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  8. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0531, Services Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  9. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  11. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2024).

  12. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  13. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  14. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  15. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  17. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  18. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  19. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  20. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  21. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  22. No harm, with potential for more than minimal harm

    Ensure that sources of ignition are removed from patients receiving respiratory therapy.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0925, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).