All citations for Truman Lake Manor Inc

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Truman Lake Manor Inc

Last standard health inspection on record

May 22, 2026

Showing 1 to 14 of 14 citations

  1. No harm, with potential for more than minimal harm

    Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0111, Construction Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  2. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  5. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  6. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  7. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  8. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  10. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  11. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  12. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

  14. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 5, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.