All citations for University Park Healthcare Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to University Park Healthcare Center

Last standard health inspection on record

April 3, 2026

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  2. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  4. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0531, Services Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  5. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  8. No harm, with potential for more than minimal harm

    Construct fire resistant interior walls.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0331, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  9. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  12. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  13. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  14. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  15. No harm, with potential for more than minimal harm

    Install properly constructed windows in hallway walls or doors.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0364, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  16. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  17. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  18. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  19. No harm, with potential for minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

  20. No harm, with potential for minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of January 25, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 18, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.