All citations for Uvalde Healthcare and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Uvalde Healthcare and Rehabilitation Center

Last standard health inspection on record

June 11, 2026

Showing 1 to 7 of 7 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  2. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2026).

  3. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2026).

  4. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2026).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2026).

  6. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2026).

  7. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of June 11, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 24, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.