All citations for Vintage Faire Nursing & Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Vintage Faire Nursing & Rehabilitation Center

Last standard health inspection on record

August 7, 2026

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Provide a means of sharing information on occupancy/needs.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0034, Emergency Preparedness Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  4. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  5. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  6. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  7. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  8. No harm, with potential for more than minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  9. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  11. No harm, with potential for minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  12. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 11, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.