All citations for Vivo Healthcare Gandy

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Vivo Healthcare Gandy

Last standard health inspection on record

January 16, 2025

Showing 26 to 31 of 31 citations

  1. No harm, with potential for more than minimal harm

    Ensure drugs and biologicals used in the facility are labeled in accordance with currently accepted professional principles; and all drugs and biologicals must be stored in locked compartments, separately locked, compartments for controlled drugs.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0761, Pharmacy Service Deficiencies. Inspection of May 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2021).

  2. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of May 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2021).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2021).

  4. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2021).

  5. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of May 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2021).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 20, 2021).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.