  1. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2023).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    A waiver was granted (July 19, 2023).

  3. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2023).

  4. No harm, with potential for more than minimal harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0926, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2023).

  5. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of December 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  6. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  7. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of August 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 6, 2024).

  8. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 6, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2023).

  10. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of December 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  11. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of December 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  12. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of August 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 6, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of August 21, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 6, 2024).

  14. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2023).

  15. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 19, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.