All citations for Waterside Health & Rehab Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Waterside Health & Rehab Center

Last standard health inspection on record

June 23, 2023

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  3. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  4. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  5. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  6. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  7. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  8. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  9. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2018).

  11. No harm, with potential for minimal harm

    Establish emergency prep training and testing.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 12, 2018).

  12. No harm, with potential for minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of June 28, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 12, 2018).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.