All citations for Waterview Heights Rehabilitation and Nursing Cente

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Waterview Heights Rehabilitation and Nursing Cente

Last standard health inspection on record

December 22, 2025

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  2. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 27, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 4, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  5. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  6. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  7. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  8. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  9. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 3, 2026).

  10. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  11. No harm, with potential for more than minimal harm

    Ensure electrical receptacles or cover plates have distinctive color or marking.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0917, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  12. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2026).

  13. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  14. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 3, 2026).

  15. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

  16. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 22, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 20, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.