All citations for Westside Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Westside Care Center

Last standard health inspection on record

June 22, 2026

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Establish policies and procedures including evacuation.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0020, Emergency Preparedness Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  2. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  3. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  4. No harm, with potential for more than minimal harm

    Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0700, Miscellaneous Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  5. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  6. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  7. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  8. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  11. No harm, with potential for more than minimal harm

    Develop Emergency Preparedness policies and procedures.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0013, Emergency Preparedness Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  12. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  13. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  14. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2022).

  15. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  16. No harm, with potential for more than minimal harm

    Have an alternate power supply for its alarm system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0344, Smoke Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  17. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  18. No harm, with potential for more than minimal harm

    Meet other general requirements that are deficient.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0500, Services Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  19. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

  20. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 19, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 16, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.