All citations for White Settlement Nursing Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to White Settlement Nursing Center

Last standard health inspection on record

July 30, 2026

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Include a process for Emergency Preparedness collaboration.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0009, Emergency Preparedness Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  2. No harm, with potential for more than minimal harm

    Establish policies and procedures for volunteers.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0024, Emergency Preparedness Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  3. No harm, with potential for more than minimal harm

    Establish roles under a Waiver declared by secretary.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0026, Emergency Preparedness Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  4. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  5. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  6. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  7. No harm, with potential for more than minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  8. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  9. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  10. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  11. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  13. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 16, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (April 13, 2026).

  14. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  15. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  16. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  17. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  18. No harm, with potential for more than minimal harm

    Have an externally vented heating system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0522, Services Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  19. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

  20. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of July 30, 2026. Found during a standard inspection.

    No plan of correction on record.

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.