All citations for Willow Springs Rehabilitation and Healthcare Cente

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Willow Springs Rehabilitation and Healthcare Cente

Last standard health inspection on record

January 8, 2026

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 22, 2024).

  3. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 19, 2024).

  4. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 17, 2024).

  5. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 26, 2024).

  6. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2024).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 24, 2024).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 26, 2024).

  9. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 1, 2024).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 15, 2024).

  11. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2024).

  12. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 1, 2024).

  13. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2024).

  14. No harm, with potential for more than minimal harm

    Install properly constructed and protected linen or trash chutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0541, Services Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 26, 2024).

  15. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 7, 2024).

  16. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 12, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 29, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.