All citations for Willowcreek Wellness & Rehabilitation

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Willowcreek Wellness & Rehabilitation

Last standard health inspection on record

August 14, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2024).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2024).

  3. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    A waiver was granted (January 11, 2025).

  4. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 8, 2024).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2024).

  6. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 8, 2024).

  7. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    A waiver was granted (January 11, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2024).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    A waiver was granted (January 11, 2025).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of August 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.