All citations for Adviniacare at Provincetown

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Adviniacare at Provincetown

Last standard health inspection on record

April 2, 2026

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  2. No harm, with potential for more than minimal harm

    Develop Emergency Preparedness policies and procedures.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0013, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  3. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  4. No harm, with potential for more than minimal harm

    Establish procedures for tracking staff and patients during an emergency.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0018, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  5. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  6. No harm, with potential for more than minimal harm

    Establish methods for sharing information.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0033, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  7. No harm, with potential for more than minimal harm

    Provide family notifications of emergency plan.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0035, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  8. No harm, with potential for more than minimal harm

    Establish emergency prep training and testing.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  9. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  10. No harm, with potential for more than minimal harm

    Meet requirements for outpatient facilities located next to inpatient facilities separated by fire resistive construction.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0132, Construction Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  11. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 9, 2026).

  12. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  13. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 9, 2026).

  14. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  15. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  16. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  17. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 2, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 30, 2026).

  18. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of February 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2024).

  19. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of February 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2024).

  20. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 15, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 12, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.