All citations for Atlee Hill Health and Rehab Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Atlee Hill Health and Rehab Center

Last standard health inspection on record

August 29, 2025

Showing 1 to 23 of 23 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  3. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  4. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  5. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  6. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  7. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  8. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  9. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  10. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  12. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  13. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  14. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  15. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 21, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 19, 2024).

  16. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  17. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  18. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  19. No harm, with potential for more than minimal harm

    Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0362, Smoke Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  20. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  21. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 29, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 31, 2025).

  22. No harm, with potential for minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of April 19, 2019. Found during a standard inspection.

    A waiver was granted (January 18, 2022).

  23. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 19, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 8, 2019).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.