All citations for Belmont Terrace Nursing and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Belmont Terrace Nursing and Rehabilitation Center

Last standard health inspection on record

June 12, 2026

Showing 1 to 14 of 14 citations

  1. No harm, with potential for more than minimal harm

    Create arrangements with other facilities to receive patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0025, Emergency Preparedness Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  2. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  3. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  5. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  6. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  7. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  8. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  9. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  10. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  12. No harm, with potential for more than minimal harm

    Meet Health Care Facilities Code mechanical requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0900, Miscellaneous Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

  14. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 12, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.