All citations for Boulder Creek Post Acute

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Boulder Creek Post Acute

Last standard health inspection on record

February 14, 2025

Showing 1 to 25 of 36 citations

  1. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  2. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  4. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of October 31, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 23, 2019).

  5. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  6. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  7. No harm, with potential for more than minimal harm

    Have restrictions on the use of highly flammable decorations.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0753, Miscellaneous Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  8. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of April 24, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (May 30, 2024).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  11. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of October 31, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 23, 2019).

  12. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 31, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 23, 2019).

  13. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  14. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  15. No harm, with potential for more than minimal harm

    Establish procedures for tracking staff and patients during an emergency.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0018, Emergency Preparedness Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  16. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  17. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  18. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  19. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  20. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  21. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  22. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  23. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  24. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

  25. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of May 20, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 23, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.