All citations for Cambridge Place

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Cambridge Place

Last standard health inspection on record

August 26, 2025

Showing 1 to 25 of 41 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  2. No harm, with potential for more than minimal harm

    Establish policies and procedures for volunteers.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0024, Emergency Preparedness Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  3. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  4. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  5. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  6. No harm, with potential for more than minimal harm

    Have a fire alarm with audible and visual signals that transmits the alarm automatically to notify emergency forces in event of fire.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0343, Smoke Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  7. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  8. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  9. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  10. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  11. No harm, with potential for more than minimal harm

    Have restrictions on the use of highly flammable decorations.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0753, Miscellaneous Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  12. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 26, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 14, 2026).

  14. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  15. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 28, 2024).

  16. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  17. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  18. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  19. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  20. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  21. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  22. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  23. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of December 11, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  24. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of March 17, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2022).

  25. No harm, with potential for more than minimal harm

    Include a process for Emergency Preparedness collaboration.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0009, Emergency Preparedness Deficiencies. Inspection of March 17, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.