All citations for CareOne At Wall

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to CareOne At Wall

Last standard health inspection on record

March 25, 2026

Showing 1 to 18 of 18 citations

  1. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 3, 2026).

  2. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 10, 2026).

  3. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 3, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 2, 2026).

  5. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 7, 2026).

  6. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 12, 2026).

  7. No harm, with potential for more than minimal harm

    Have proper fire barriers, ventilation and signs for the transfilling of oxygen.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0927, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 25, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2026).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 30, 2024).

  9. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 30, 2024).

  11. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 6, 2024).

  12. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of October 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 30, 2023).

  13. No harm, with potential for more than minimal harm

    Properly provide smoke detection systems in areas open to corridors.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0347, Smoke Deficiencies. Inspection of October 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2024).

  14. No harm, with potential for more than minimal harm

    Enure that solid fuel-burning fireplaces are not in patient sleeping areas.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0525, Services Deficiencies. Inspection of October 17, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2024).

  15. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 30, 2024).

  16. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 30, 2024).

  17. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 6, 2024).

  18. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0531, Services Deficiencies. Inspection of October 18, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.