All citations for Cayuga Nursing and Rehabilitation Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Cayuga Nursing and Rehabilitation Center

Last standard health inspection on record

January 24, 2025

Showing 1 to 21 of 21 citations

  1. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  3. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  4. No harm, with potential for more than minimal harm

    Install a two-hour-resistant firewall separation.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0133, Construction Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  5. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  7. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  8. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of July 30, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 28, 2021).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 30, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 28, 2021).

  10. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  11. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  12. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  13. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  14. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  15. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  16. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 24, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2025).

  17. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  18. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  19. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  20. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

  21. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 8, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 6, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.