All citations for Chestnut Hill Rehabilitation and Healthcare Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Chestnut Hill Rehabilitation and Healthcare Center

Last standard health inspection on record

February 27, 2026

Showing 1 to 22 of 22 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 27, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2026).

  2. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  4. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  6. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of February 27, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2026).

  7. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of February 27, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2026).

  8. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 27, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2026).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 27, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2026).

  10. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 27, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 25, 2026).

  11. No harm, with potential for more than minimal harm

    Provide primary/alternate means for communication.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0032, Emergency Preparedness Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  12. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  13. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  14. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  15. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  16. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 28, 2025).

  17. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  18. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  19. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  20. No harm, with potential for minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  21. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

  22. No harm, with potential for minimal harm

    Meet requirements for the use of electrical equipment.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 2, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.