All citations for Clover Meadows Healthcare and Rehabilitation Cente

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Clover Meadows Healthcare and Rehabilitation Cente

Last standard health inspection on record

June 26, 2026

Showing 1 to 11 of 11 citations

  1. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 4, 2025).

  2. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 4, 2025).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 7, 2025).

  4. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of January 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 4, 2025).

  5. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 4, 2025).

  6. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of October 31, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2023).

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 31, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2023).

  8. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of October 31, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2023).

  9. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of October 31, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2023).

  10. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 31, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2023).

  11. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 16, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 4, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.