All citations for Crown Center at Laurel Lake
State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.
Last standard health inspection on record
April 16, 2026
Showing 1 to 14 of 14 citations
No harm, with potential for more than minimal harm
Have a battery powered remote alarm panel in a location accessible by operating personnel.
The home gave a date the problem would be corrected (May 4, 2026).
No harm, with potential for more than minimal harm
Install emergency lighting that can last at least 1 1/2 hours.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
Have approved installation, maintenance and testing program for fire alarm systems.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
Inspect, test, and maintain automatic sprinkler systems.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
Satisfy building requirements after a repair, renovation, modification, or change of user/occupancy.
The home gave a date the problem would be corrected (May 4, 2026).
No harm, with potential for more than minimal harm
Install an approved automatic sprinkler system.
The home gave a date the problem would be corrected (May 4, 2026).
No harm, with potential for more than minimal harm
Install corridor and hallway doors that block smoke.
The home gave a date the problem would be corrected (October 19, 2023).
No harm, with potential for more than minimal harm
Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
The home gave a date the problem would be corrected (September 17, 2021).
No harm, with potential for more than minimal harm
Have properly installed electrical wiring and gas equipment.
The home gave a date the problem would be corrected (September 17, 2021).
No harm, with potential for more than minimal harm
Ensure proper usage of power strips and extension cords.
The home gave a date the problem would be corrected (September 17, 2021).
No harm, with potential for more than minimal harm
Have proper medical gas storage and administration areas.
The home gave a date the problem would be corrected (September 17, 2021).
Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.