All citations for Deerings Nursing and Rehabilitation

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Deerings Nursing and Rehabilitation

Last standard health inspection on record

May 21, 2026

Showing 1 to 15 of 15 citations

  1. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  2. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  3. No harm, with potential for more than minimal harm

    Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

    Pattern (more than a few residents). CMS level E.

    Health citation F-0812, Nutrition and Dietary Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2026).

  4. No harm, with potential for more than minimal harm

    Provide bedrooms that don't allow residents to see each other when privacy is needed.

    Pattern (more than a few residents). CMS level E.

    Health citation F-0914, Environmental Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2026).

  5. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  7. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  8. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  9. No harm, with potential for more than minimal harm

    Meet requirements for the use and maintenance of medical gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0922, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  10. No harm, with potential for more than minimal harm

    Ensure that a nursing home area is free from accident hazards and provides adequate supervision to prevent accidents.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0689, Quality of Life and Care Deficiencies. Inspection of June 25, 2026. Found during a complaint inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

  11. No harm, with potential for more than minimal harm

    Assess the resident when there is a significant change in condition

    Isolated (one or a few residents). CMS level D.

    Health citation F-0637, Resident Assessment and Care Planning Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2026).

  12. No harm, with potential for more than minimal harm

    Provide appropriate pressure ulcer care and prevent new ulcers from developing.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0686, Quality of Life and Care Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2026).

  13. No harm, with potential for more than minimal harm

    Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0755, Pharmacy Service Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 15, 2026).

  14. No harm, with potential for more than minimal harm

    Ensure the transfer/discharge meets the resident's needs/preferences and that the resident is prepared for a safe transfer/discharge.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0627, Resident Rights Deficiencies. Inspection of November 10, 2025. Found during a complaint inspection.

    The home gave a date the problem would be corrected (December 5, 2025).

  15. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 21, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 28, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.