All citations for Elderwood at North Creek

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Elderwood at North Creek

Last standard health inspection on record

September 20, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 22 of 22 citations

  1. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 18, 2024).

  2. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 18, 2024).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 18, 2024).

  4. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of September 19, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 16, 2024).

  5. No harm, with potential for more than minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of September 19, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 16, 2024).

  6. No harm, with potential for more than minimal harm

    Address patient/client population and determine types of services needed.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0007, Emergency Preparedness Deficiencies. Inspection of September 19, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 16, 2024).

  7. No harm, with potential for more than minimal harm

    Include a process for Emergency Preparedness collaboration.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0009, Emergency Preparedness Deficiencies. Inspection of September 19, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 16, 2024).

  8. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of September 19, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 16, 2024).

  9. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 8, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  10. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 18, 2024).

  11. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 18, 2024).

  12. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 18, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 8, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  14. No harm, with potential for more than minimal harm

    Ensure that testing and maintenance of electrical equipment is performed.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0921, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 8, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2022).

  15. No harm, with potential for more than minimal harm

    Establish roles under a Waiver declared by secretary.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0026, Emergency Preparedness Deficiencies. Inspection of November 1, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2019).

  16. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of November 1, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2019).

  17. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of November 1, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2019).

  18. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of November 1, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2019).

  19. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 22, 2024).

  20. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0531, Services Deficiencies. Inspection of September 20, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  21. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of November 1, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2019).

  22. No harm, with potential for minimal harm

    Include a process for Emergency Preparedness collaboration.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0009, Emergency Preparedness Deficiencies. Inspection of November 1, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 30, 2019).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.