All citations for Envive of River City

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Envive of River City

Last standard health inspection on record

January 7, 2026

Showing 1 to 24 of 24 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of January 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2026).

  2. No harm, with potential for more than minimal harm

    Develop Emergency Preparedness policies and procedures.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0013, Emergency Preparedness Deficiencies. Inspection of January 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2026).

  3. No harm, with potential for more than minimal harm

    Develop a communication plan.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0029, Emergency Preparedness Deficiencies. Inspection of January 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2026).

  4. No harm, with potential for more than minimal harm

    Establish emergency prep training and testing.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of January 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2026).

  5. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  6. No harm, with potential for more than minimal harm

    Develop Emergency Preparedness policies and procedures.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0013, Emergency Preparedness Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  7. No harm, with potential for more than minimal harm

    Develop a communication plan.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0029, Emergency Preparedness Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  8. No harm, with potential for more than minimal harm

    Establish emergency prep training and testing.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  9. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  10. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  11. No harm, with potential for more than minimal harm

    Meet other general requirements that are deficient.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0300, Egress Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  12. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2026).

  14. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 7, 2026).

  15. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  16. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  17. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  18. No harm, with potential for minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  19. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of October 11, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (November 15, 2024).

  20. No harm, with potential for minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home has a plan to correct it (August 24, 2023).

  21. No harm, with potential for minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home has a plan to correct it (August 9, 2023).

  22. No harm, with potential for minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home has a plan to correct it (August 9, 2023).

  23. No harm, with potential for minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home has a plan to correct it (August 1, 2023).

  24. No harm, with potential for minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level B.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.