All citations for Excel Care at the Pines
State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.
Last standard health inspection on record
April 6, 2026
Showing 1 to 25 of 30 citations
No harm, with potential for more than minimal harm
Install emergency lighting that can last at least 1 1/2 hours.
The home gave a date the problem would be corrected (May 15, 2026).
No harm, with potential for more than minimal harm
Have approved installation, maintenance and testing program for fire alarm systems.
The home gave a date the problem would be corrected (May 10, 2026).
No harm, with potential for more than minimal harm
Inspect, test, and maintain automatic sprinkler systems.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
Have elevators that firefighters can control in the event of a fire.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
To conduct inspection, testing and maintenance of fire doors by qualified individuals.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
Ensure that testing and maintenance of electrical equipment is performed.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
Develop and maintain an Emergency Preparedness Program (EP).
The home gave a date the problem would be corrected (January 3, 2025).
No harm, with potential for more than minimal harm
Install proper backup exit lighting.
The home gave a date the problem would be corrected (January 10, 2025).
No harm, with potential for more than minimal harm
Have approved installation, maintenance and testing program for fire alarm systems.
The home gave a date the problem would be corrected (January 10, 2025).
No harm, with potential for more than minimal harm
Install an approved automatic sprinkler system.
The home gave a date the problem would be corrected (December 1, 2024).
No harm, with potential for more than minimal harm
Ensure that corridors are separated from use areas by walls constructed to limit the passage of smoke.
The home gave a date the problem would be corrected (March 18, 2025).
No harm, with potential for more than minimal harm
Meet requirements for the installation and maintenance of electrical systems.
The home gave a date the problem would be corrected (January 10, 2025).
No harm, with potential for more than minimal harm
Have a battery powered remote alarm panel in a location accessible by operating personnel.
The home gave a date the problem would be corrected (December 25, 2024).
No harm, with potential for more than minimal harm
Have generator or other power source capable of supplying service within 10 seconds.
The home gave a date the problem would be corrected (January 3, 2025).
No harm, with potential for more than minimal harm
Ensure that testing and maintenance of electrical equipment is performed.
The home gave a date the problem would be corrected (January 3, 2025).
No harm, with potential for more than minimal harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
The home gave a date the problem would be corrected (May 15, 2026).
No harm, with potential for more than minimal harm
Install corridor and hallway doors that block smoke.
The home gave a date the problem would be corrected (June 9, 2026).
No harm, with potential for more than minimal harm
Ensure precautions for handling oxygen cylinders and equipment are correctly followed.
The home gave a date the problem would be corrected (May 21, 2026).
No harm, with potential for more than minimal harm
Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
The home gave a date the problem would be corrected (January 3, 2025).
No harm, with potential for more than minimal harm
Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
The home gave a date the problem would be corrected (January 3, 2025).
No harm, with potential for more than minimal harm
Install emergency lighting that can last at least 1 1/2 hours.
The home gave a date the problem would be corrected (September 30, 2023).
No harm, with potential for more than minimal harm
Install an approved automatic sprinkler system.
The home gave a date the problem would be corrected (September 30, 2023).
No harm, with potential for more than minimal harm
Have properly sized and located compartments to protect residents from smoke.
The home gave a date the problem would be corrected (September 30, 2023).
Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.