All citations for Ferncliff Nursing Home Co Inc

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Ferncliff Nursing Home Co Inc

Last standard health inspection on record

February 27, 2025

Showing 1 to 12 of 12 citations

  1. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 13, 2025).

  2. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 15, 2024).

  3. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 15, 2024).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 15, 2024).

  5. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of April 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 9, 2021).

  6. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of April 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 9, 2021).

  7. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of February 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2025).

  8. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of February 27, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 14, 2025).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 15, 2024).

  10. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of April 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 9, 2021).

  11. No harm, with potential for more than minimal harm

    Install proper backup exit lighting.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0281, Egress Deficiencies. Inspection of April 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 9, 2021).

  12. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 20, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 9, 2021).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.