All citations for FT Washington Rehabilitation and Wellness Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to FT Washington Rehabilitation and Wellness Center

Last standard health inspection on record

November 25, 2025

Showing 1 to 25 of 27 citations

  1. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  2. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2026).

  5. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2026).

  6. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2026).

  8. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2024).

  9. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  10. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2024).

  11. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 17, 2024).

  12. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  13. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  14. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  15. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2026).

  16. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  17. No harm, with potential for more than minimal harm

    Meet other general requirements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  18. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  19. No harm, with potential for more than minimal harm

    Have elevators that firefighters can control in the event of a fire.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0531, Services Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  20. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 15, 2026).

  21. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 25, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 6, 2026).

  22. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 2, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 26, 2024).

  23. No harm, with potential for more than minimal harm

    Have an externally vented heating system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0522, Services Deficiencies. Inspection of April 17, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 31, 2019).

  24. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 17, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 31, 2019).

  25. No harm, with potential for minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 17, 2019. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 31, 2019).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.