All citations for Glenwood Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Glenwood Center

Last standard health inspection on record

February 28, 2024

This is more than 2 years ago. Newer inspection results may not be on record yet, so the results below may not describe the home today. Ask the home for its most recent inspection report.

Showing 1 to 17 of 17 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of February 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  3. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of February 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  4. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  5. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of February 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  6. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  8. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  9. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of November 8, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2018).

  10. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of February 28, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 5, 2024).

  11. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  12. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  13. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  14. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 23, 2020. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 5, 2020).

  15. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of November 8, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2018).

  16. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of November 8, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2018).

  17. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 8, 2018. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 13, 2018).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.