State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Good Samaritan - Davenport

Last standard health inspection on record

January 29, 2026

Showing 1 to 19 of 19 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of January 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 10, 2026).

  2. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of January 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 10, 2026).

  3. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 10, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 10, 2026).

  5. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of January 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 12, 2026).

  6. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 15, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 22, 2025).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 15, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 23, 2025).

  8. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 15, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 5, 2025).

  9. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2024).

  10. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  11. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  12. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  13. No harm, with potential for more than minimal harm

    Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0354, Smoke Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  14. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  15. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  16. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 28, 2024).

  17. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of January 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 29, 2026).

  18. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 15, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 5, 2025).

  19. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 14, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 29, 2024).