All citations for Greenwood Center for Rehabilitation and Nursing

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Greenwood Center for Rehabilitation and Nursing

Last standard health inspection on record

January 8, 2026

Showing 1 to 21 of 21 citations

  1. No harm, with potential for more than minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  2. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  3. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of January 8, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2026).

  4. No harm, with potential for more than minimal harm

    Have properly installed hallway dispensers for alcohol-based hand rub.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0325, Smoke Deficiencies. Inspection of January 8, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2026).

  5. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of January 8, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2026).

  6. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of January 8, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2026).

  7. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 8, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 17, 2026).

  8. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2024).

  9. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2024).

  11. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2024).

  12. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 29, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2024).

  13. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  14. No harm, with potential for minimal harm

    Establish an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0001, Emergency Preparedness Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  15. No harm, with potential for minimal harm

    Meet other general requirements.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0100, Construction Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  16. No harm, with potential for minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  17. No harm, with potential for minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  18. No harm, with potential for minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  19. No harm, with potential for minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  20. No harm, with potential for minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0521, Services Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).

  21. No harm, with potential for minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 22, 2025).