All citations for Gulfport Nursing Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Gulfport Nursing Center

Last standard health inspection on record

June 13, 2025

Showing 1 to 10 of 10 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 11, 2025).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 13, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 11, 2025).

  3. No harm, with potential for more than minimal harm

    Establish emergency prep training and testing.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2023).

  4. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2023).

  5. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 30, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2023).

  6. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of July 1, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2021).

  7. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of July 1, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2021).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 1, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2021).

  9. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 1, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2021).

  10. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of July 1, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 31, 2021).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.