All citations for Harmar Village Health & Rehab Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Harmar Village Health & Rehab Center

Last standard health inspection on record

April 3, 2026

Showing 1 to 23 of 23 citations

  1. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

  3. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of April 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

  4. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  5. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  7. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  8. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  9. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  10. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of April 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

  11. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of April 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

  12. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

  13. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  14. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 17, 2024).

  15. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  16. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  17. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  18. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0521, Services Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  19. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  20. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 1, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 21, 2023).

  21. No harm, with potential for minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  22. No harm, with potential for minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

  23. No harm, with potential for minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of March 14, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 14, 2025).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.