State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Harmony Waterloo

Last standard health inspection on record

January 14, 2026

Showing 1 to 20 of 20 citations

  1. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 10, 2024).

  2. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  3. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 24, 2024).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 7, 2024).

  5. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 6, 2024).

  6. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 24, 2024).

  7. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

  8. No harm, with potential for more than minimal harm

    Honor the resident's right to a dignified existence, self-determination, communication, and to exercise his or her rights.

    Pattern (more than a few residents). CMS level E.

    Health citation F-0550, Resident Rights Deficiencies. Inspection of August 8, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (August 22, 2024).

  9. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 17, 2024).

  11. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  12. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 7, 2024).

  13. No harm, with potential for more than minimal harm

    Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

    Pattern (more than a few residents). CMS level E.

    Health citation F-0584, Resident Rights Deficiencies. Inspection of October 18, 2023. Found during a complaint inspection.

    The home gave a date the problem would be corrected (November 9, 2023).

  14. No harm, with potential for more than minimal harm

    Provide pharmaceutical services to meet the needs of each resident and employ or obtain the services of a licensed pharmacist.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0755, Pharmacy Service Deficiencies. Inspection of August 8, 2024. Found during a complaint inspection.

    The home gave a date the problem would be corrected (August 22, 2024).

  15. No harm, with potential for more than minimal harm

    Honor the resident's right to a safe, clean, comfortable and homelike environment, including but not limited to receiving treatment and supports for daily living safely.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0584, Resident Rights Deficiencies. Inspection of May 22, 2024. Found during a standard inspection and a complaint inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  16. No harm, with potential for more than minimal harm

    Provide care and assistance to perform activities of daily living for any resident who is unable.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0677, Quality of Life and Care Deficiencies. Inspection of May 22, 2024. Found during a standard inspection and a complaint inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  17. No harm, with potential for more than minimal harm

    Provide safe and appropriate respiratory care for a resident when needed.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0695, Quality of Life and Care Deficiencies. Inspection of May 22, 2024. Found during a standard inspection and a complaint inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  18. No harm, with potential for more than minimal harm

    Procure food from sources approved or considered satisfactory and store, prepare, distribute and serve food in accordance with professional standards.

    Isolated (one or a few residents). CMS level D.

    Health citation F-0812, Nutrition and Dietary Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 12, 2024).

  19. No harm, with potential for more than minimal harm

    Meet requirements for operating features, such as evacuation plans, fire drills, smoking regulations, draperies, decorations and the inspection, testing and maintenance of fire doors.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0700, Miscellaneous Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 29, 2024).

  20. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 22, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 7, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.