All citations for Hazel Hawkins Memorial Hospital D/P SNF

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Hazel Hawkins Memorial Hospital D/P SNF

Last standard health inspection on record

September 19, 2025

Showing 1 to 25 of 32 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  2. No harm, with potential for more than minimal harm

    Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0342, Smoke Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  3. No harm, with potential for more than minimal harm

    Follow proper procedures when the fire alarm was out of service for more than 4 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0346, Smoke Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  5. No harm, with potential for more than minimal harm

    Establish roles under a Waiver declared by secretary.

    Pattern (more than a few residents). CMS level E.

    Emergency preparedness citation E-0026, Emergency Preparedness Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  7. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  8. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  9. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  10. No harm, with potential for more than minimal harm

    Ensure that personnel concerned with handling of medical gases and cylinders are trained on the risk.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0926, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  11. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  12. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  13. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  14. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  15. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of September 19, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 1, 2025).

  16. No harm, with potential for more than minimal harm

    Use approved construction type or materials.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0161, Construction Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  17. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  18. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  19. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  20. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  21. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  22. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 19, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 3, 2024).

  23. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of June 24, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2022).

  24. No harm, with potential for more than minimal harm

    Establish procedures for tracking staff and patients during an emergency.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0018, Emergency Preparedness Deficiencies. Inspection of June 24, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2022).

  25. No harm, with potential for more than minimal harm

    Establish policies and procedures for sheltering.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0022, Emergency Preparedness Deficiencies. Inspection of June 24, 2022. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 26, 2022).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.