All citations for Heritage at Turner Park Health & Rehab

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Heritage at Turner Park Health & Rehab

Last standard health inspection on record

July 31, 2025

Showing 1 to 25 of 40 citations

  1. No harm, with potential for more than minimal harm

    Include a process for Emergency Preparedness collaboration.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0009, Emergency Preparedness Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  2. No harm, with potential for more than minimal harm

    List the names and contact information of those in the facility.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0030, Emergency Preparedness Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  3. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  4. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  5. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  6. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  7. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  8. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  9. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  10. No harm, with potential for more than minimal harm

    Have an externally vented heating system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0522, Services Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  11. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 31, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 31, 2025).

  13. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  14. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  15. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  16. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  17. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  18. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  19. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  20. No harm, with potential for more than minimal harm

    Have posted "No-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0741, Miscellaneous Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 25, 2024).

  21. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 21, 2024).

  22. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 26, 2023).

  23. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 26, 2023).

  24. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of April 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 26, 2023).

  25. No harm, with potential for more than minimal harm

    Meet requirements for the installation and maintenance of electrical systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0911, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 13, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 26, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.