All citations for John J Kane Regional Center-Gl

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to John J Kane Regional Center-Gl

Last standard health inspection on record

July 9, 2026

Showing 1 to 16 of 16 citations

  1. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of July 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 13, 2026).

  2. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 13, 2026).

  3. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of July 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 13, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of June 6, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 2, 2025).

  5. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2024).

  6. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of July 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 13, 2026).

  7. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of June 6, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 2, 2025).

  8. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of June 6, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 2, 2025).

  9. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of June 6, 2025. Found during a standard inspection.

    The home has a plan to correct it (July 2, 2025).

  10. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 6, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (July 2, 2025).

  11. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of July 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2024).

  12. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of July 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2024).

  13. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of July 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2024).

  14. No harm, with potential for more than minimal harm

    Have power receptacles that are properly grounded.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0912, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 26, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 20, 2024).

  15. No harm, with potential for minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of July 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 13, 2026).

  16. No harm, with potential for minimal harm

    Establish roles under a Waiver declared by secretary.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0026, Emergency Preparedness Deficiencies. Inspection of July 9, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 13, 2026).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.