All citations for Kewaunee Health Services

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Kewaunee Health Services

Last standard health inspection on record

June 29, 2026

Showing 1 to 21 of 21 citations

  1. No harm, with potential for more than minimal harm

    Conduct risk assessment and an All-Hazards approach.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0006, Emergency Preparedness Deficiencies. Inspection of June 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2026).

  2. No harm, with potential for more than minimal harm

    Have a battery powered remote alarm panel in a location accessible by operating personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0916, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 15, 2026).

  3. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (October 15, 2026).

  4. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 15, 2025).

  5. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 29, 2025).

  6. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 19, 2025).

  7. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 15, 2025).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    A waiver was granted (May 15, 2025).

  9. No harm, with potential for more than minimal harm

    Conduct testing and exercise requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0039, Emergency Preparedness Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  10. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  13. No harm, with potential for more than minimal harm

    Have proper fire barriers, ventilation and signs for the transfilling of oxygen.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0927, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of June 29, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (August 5, 2026).

  14. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 2, 2025).

  15. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 21, 2025).

  16. No harm, with potential for more than minimal harm

    Have an enclosure around a vertical opening shaft.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0311, Smoke Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  17. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  18. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  19. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

  20. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 8, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 30, 2025).

  21. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (April 4, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.