All citations for La Sierra Care Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to La Sierra Care Center

Last standard health inspection on record

January 23, 2026

Showing 1 to 23 of 23 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of January 23, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 29, 2026).

  2. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 23, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 12, 2026).

  3. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 23, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 29, 2026).

  4. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  5. No harm, with potential for more than minimal harm

    Install smoke barrier doors that can resist smoke for at least 20 minutes.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0374, Smoke Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  6. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  8. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 23, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (January 30, 2026).

  9. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  10. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  11. No harm, with potential for more than minimal harm

    Address patient/client population and determine types of services needed.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0007, Emergency Preparedness Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  12. No harm, with potential for more than minimal harm

    Establish procedures for tracking staff and patients during an emergency.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0018, Emergency Preparedness Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  13. No harm, with potential for more than minimal harm

    Establish policies and procedures for medical documentation.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0023, Emergency Preparedness Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  14. No harm, with potential for more than minimal harm

    Establish policies and procedures for volunteers.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0024, Emergency Preparedness Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  15. No harm, with potential for more than minimal harm

    Establish emergency prep training and testing.

    Isolated (one or a few residents). CMS level D.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  16. No harm, with potential for more than minimal harm

    Have corridors or aisles that are unobstructed and are at least 8 feet in width.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0232, Egress Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  17. No harm, with potential for more than minimal harm

    Have properly located and lighted "Exit" signs.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0293, Egress Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  18. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  19. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  20. No harm, with potential for more than minimal harm

    Provide a written emergency evacuation plan.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0711, Miscellaneous Deficiencies. Inspection of April 29, 2021. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 18, 2021).

  21. No harm, with potential for minimal harm

    Establish policies and procedures for medical documentation.

    Widespread (many residents). CMS level C.

    Emergency preparedness citation E-0023, Emergency Preparedness Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  22. No harm, with potential for minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

  23. No harm, with potential for minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level C.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of August 23, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 4, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.