All citations for Lexington Park Nursing & Post Acute Center

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Lexington Park Nursing & Post Acute Center

Last standard health inspection on record

April 29, 2026

Showing 1 to 25 of 45 citations

  1. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  2. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  3. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  4. No harm, with potential for more than minimal harm

    Establish emergency prep training and testing.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0036, Emergency Preparedness Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  5. No harm, with potential for more than minimal harm

    Establish staff and initial training requirements.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0037, Emergency Preparedness Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  6. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 13, 2024).

  7. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 13, 2024).

  8. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0521, Services Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  9. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  10. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  11. No harm, with potential for more than minimal harm

    Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0901, Electrical Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  12. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  13. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 28, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2023).

  14. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 28, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2023).

  15. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of March 28, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2023).

  16. No harm, with potential for more than minimal harm

    Ensure that building systems meet requirements determined by risk assessment procedures performed by qualified personnel.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0901, Electrical Deficiencies. Inspection of March 28, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2023).

  17. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 28, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2023).

  18. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 28, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 22, 2023).

  19. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  20. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  21. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  22. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0511, Services Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  23. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of April 29, 2026. Found during a standard inspection.

    The home has a plan to correct it (July 16, 2026).

  24. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

  25. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of July 17, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (September 11, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.