All citations for Life Care Center of Cheyenne

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Life Care Center of Cheyenne

Last standard health inspection on record

November 18, 2025

Showing 1 to 22 of 22 citations

  1. No harm, with potential for more than minimal harm

    Provide emergency officials' contact information.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0031, Emergency Preparedness Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  2. No harm, with potential for more than minimal harm

    Implement emergency and standby power systems.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0041, Emergency Preparedness Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 12, 2025).

  3. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  4. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  5. No harm, with potential for more than minimal harm

    To conduct inspection, testing and maintenance of fire doors by qualified individuals.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0761, Miscellaneous Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  6. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  7. No harm, with potential for more than minimal harm

    Meet Health Care Facilities Code mechanical requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0900, Miscellaneous Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    A waiver was granted (August 2, 2024).

  8. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of March 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 23, 2023).

  9. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of March 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2023).

  10. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  11. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  12. No harm, with potential for more than minimal harm

    Have exits that are accessible at all times.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0271, Egress Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  13. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  14. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  15. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  16. No harm, with potential for more than minimal harm

    Properly select, install, inspect, or maintain portable fire extinguishes.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0355, Smoke Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  17. No harm, with potential for more than minimal harm

    Have restrictions on the use of portable space heaters.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0781, Miscellaneous Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  18. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of November 18, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (December 10, 2025).

  19. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of June 6, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (June 27, 2024).

  20. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of March 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2023).

  21. No harm, with potential for more than minimal harm

    Meet requirements for the use of electrical equipment.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0919, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 3, 2023).

  22. No harm, with potential for more than minimal harm

    Have proper medical gas storage and administration areas.

    Isolated (one or a few residents). CMS level D.

    Fire safety citation K-0923, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of March 2, 2023. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 1, 2023).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of October 1, 2026. Inspection results describe the home at the time of each inspection.