All citations for Little Sisters of the Poor

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Little Sisters of the Poor

Last standard health inspection on record

May 7, 2026

Showing 1 to 19 of 19 citations

  1. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of May 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 13, 2026).

  2. No harm, with potential for more than minimal harm

    Have properly installed electrical wiring and gas equipment.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0511, Services Deficiencies. Inspection of May 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 13, 2026).

  3. No harm, with potential for more than minimal harm

    Address subsistence needs for staff and patients.

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0015, Emergency Preparedness Deficiencies. Inspection of March 7, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 24, 2025).

  4. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of March 7, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 26, 2025).

  5. No harm, with potential for more than minimal harm

    Install an approved automatic sprinkler system.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0351, Smoke Deficiencies. Inspection of March 7, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2025).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of March 7, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 21, 2025).

  7. No harm, with potential for more than minimal harm

    Properly install and monitor supervisory attachments on automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0352, Smoke Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2024).

  8. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 8, 2024).

  9. No harm, with potential for more than minimal harm

    Have simulated fire drills held at unexpected times.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0712, Miscellaneous Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 6, 2024).

  10. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 16, 2024).

  11. No harm, with potential for more than minimal harm

    Keep aisles, corridors, and exits free of obstruction in case of emergency.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0211, Egress Deficiencies. Inspection of May 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 13, 2026).

  12. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of May 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 13, 2026).

  13. No harm, with potential for more than minimal harm

    Ensure proper usage of power strips and extension cords.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0920, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of May 7, 2026. Found during a standard inspection.

    The home gave a date the problem would be corrected (May 13, 2026).

  14. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of March 7, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2025).

  15. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of March 7, 2025. Found during a standard inspection.

    The home gave a date the problem would be corrected (March 20, 2025).

  16. No harm, with potential for more than minimal harm

    Have stairways and smokeproof enclosures used as exits that meet safety requirements.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0225, Egress Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 6, 2024).

  17. No harm, with potential for more than minimal harm

    Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0321, Smoke Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 6, 2024).

  18. No harm, with potential for more than minimal harm

    Install corridor and hallway doors that block smoke.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0363, Smoke Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 6, 2024).

  19. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of February 8, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 6, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.