All citations for Locust Ridge Healthcare LLC

State inspectors check nursing homes that take Medicare or Medicaid against federal rules, usually about once a year, and also look into complaints. Each rule a home did not meet is a citation.

Back to Locust Ridge Healthcare LLC

Last standard health inspection on record

May 14, 2026

Showing 1 to 13 of 13 citations

  1. No harm, with potential for more than minimal harm

    Develop and maintain an Emergency Preparedness Program (EP).

    Widespread (many residents). CMS level F.

    Emergency preparedness citation E-0004, Emergency Preparedness Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  2. No harm, with potential for more than minimal harm

    Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0222, Egress Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  3. No harm, with potential for more than minimal harm

    Install emergency lighting that can last at least 1 1/2 hours.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0291, Egress Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  4. No harm, with potential for more than minimal harm

    Install a fire alarm system that can be heard throughout the facility.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0341, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  5. No harm, with potential for more than minimal harm

    Have approved installation, maintenance and testing program for fire alarm systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0345, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  6. No harm, with potential for more than minimal harm

    Inspect, test, and maintain automatic sprinkler systems.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0353, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  7. No harm, with potential for more than minimal harm

    Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0914, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  8. No harm, with potential for more than minimal harm

    Have generator or other power source capable of supplying service within 10 seconds.

    Widespread (many residents). CMS level F.

    Fire safety citation K-0918, Gas, Vacuum, and Electrical Systems Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  9. No harm, with potential for more than minimal harm

    Honor the resident's right to manage his or her financial affairs.

    Pattern (more than a few residents). CMS level E.

    Health citation F-0567, Resident Rights Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  10. No harm, with potential for more than minimal harm

    Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0223, Egress Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  11. No harm, with potential for more than minimal harm

    Provide properly protected cooking facilities.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0324, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  12. No harm, with potential for more than minimal harm

    Ensure smoke barriers are constructed to a 1 hour fire resistance rating.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0372, Smoke Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

  13. No harm, with potential for more than minimal harm

    Ensure heating and ventilation systems that have been properly installed according to the manufacturer's instructions.

    Pattern (more than a few residents). CMS level E.

    Fire safety citation K-0521, Services Deficiencies. Inspection of January 31, 2024. Found during a standard inspection.

    The home gave a date the problem would be corrected (February 29, 2024).

Source: CMS Provider Information, Fire Safety Deficiencies, Health Deficiencies, Citation Code Look-up, data as of September 30, 2026. Inspection results describe the home at the time of each inspection.